Buying guide · Circuit protection

    How to choose an MCB for home circuits

    You do not choose one MCB for a house; you choose one per circuit. The rating has to sit between two numbers: at or above the design current of what is on the circuit, and at or below the current-carrying capacity of the cable protecting it. For most Indian homes that means a C curve MCB at 6 A for lighting, 16 A for general socket circuits, and 16 to 20 A on a dedicated 1.5 ton air-conditioner point. Because the cable sets the upper limit, an MCB cannot honestly be chosen without knowing what cable is behind it.

    Written by the counter team at New Delhi Electricals · Published 1 September 2026

    The rule that decides everything else

    An MCB is not protecting the appliance. It is protecting the cable. That single fact resolves most of the confusion around choosing one.

    A cable of a given size can carry a certain current continuously without overheating, and that figure depends on the size, how the cable is installed, how it is grouped with others and how warm the space is. The MCB sits in front of it to make sure the cable is never asked to carry more than that for long enough to matter. So the rating has to satisfy two conditions at once:

    • At or above the design current of the circuit, or it trips during normal use and everyone learns to ignore it.
    • At or below the current-carrying capacity of the cable in its actual installed conditions, or the cable can overheat while the MCB sits there perfectly happy.

    The second condition is the one that gets broken. Someone puts a 32 A MCB on a circuit wired in 1.5 sq mm to stop nuisance tripping, and has quietly removed the protection the cable depended on. If you take one thing from this page: the wire size and the MCB rating are one decision, not two.

    Five steps to a rating

    1. Work out what is on the circuit

    Add up the loads the circuit will realistically carry at the same time. Appliance nameplates give either watts or a rated current; at a nominal 230 V single phase, current in amps is roughly watts divided by 230. A 3 kW geyser is therefore around 13 A, and a circuit of general sockets is judged on what actually runs together, not on the theoretical maximum of every outlet at once.

    2. Find the ceiling the cable sets

    This is the step people skip. The cable already run to that point has a capacity, and the MCB cannot exceed it. If the circuit is being designed now, the two are chosen together: the load sets the cable, the cable sets the ceiling, and the MCB lands between them.

    3. Pick the nearest standard rating in between

    MCBs come in standard steps. The ratings in our catalogue are 6, 10, 16, 20, 25, 32, 40 and 63 A. Choose the smallest standard rating that clears the design current comfortably, rather than the largest one the cable would tolerate.

    4. Choose the trip curve

    C curve is the general-purpose choice for Indian homes and covers mixed sockets, motors and air conditioners. B curve suits purely resistive loads such as lighting and heating. D curve is for heavy inductive starting loads and is unusual in a home. The MCBs we carry are C curve. Curve and rating are separate decisions. See the fuller explanation in our MCB vs MCCB guide.

    5. Choose the number of poles

    Single pole switches the live conductor only, and is the usual choice for lighting and general socket circuits on a single-phase supply. Double pole switches live and neutral together, which is what you want on a dedicated high-load appliance point such as a geyser or an air conditioner, because it isolates the appliance completely. Triple and four pole devices belong on three-phase circuits and board incomers.

    Typical ratings by circuit

    What appears on most Indian domestic board schedules, indicative not prescriptive
    CircuitUsual MCBPolesNotes
    Lighting and fan points6 A, C curveSingle poleSeveral points share one circuit
    General 6 A socket circuit10 to 16 A, C curveSingle poleRating follows the cable size on the circuit
    16 A power sockets, kitchen appliances16 to 20 A, C curveSingle or double poleKitchens often get a circuit of their own
    Geyser / water heater point16 A, C curve (for a 3 kW heater)Double poleDedicated circuit; double pole so it isolates fully
    1.5 ton air-conditioner point16 to 20 A, C curveDouble poleSee the section below
    Distribution board incomer40 to 63 A, or an isolatorDouble or four poleSized against the board, not any one circuit

    These are the ratings that recur on domestic schedules. The rating for your circuit comes from its design current and its cable, which is why your electrician’s board schedule beats any table.

    Which MCB for a 1.5 ton AC?

    A 16 A or 20 A C curve MCB, double pole, on a dedicated circuit: that is the answer on most Indian domestic schedules. The reasoning behind it is more useful than the number, because it tells you when the number is wrong.

    A 1.5 ton split air conditioner draws somewhere around 7 to 10 A while running, and considerably less than that on an inverter unit at part load. What sets the MCB is not the running current but the brief surge as the compressor starts. That is exactly what the C curve exists for: it tolerates a short starting inrush without treating it as a short circuit, so a correctly rated C curve device does not trip every time the compressor kicks in.

    Air-conditioner points: the pattern, with the caveat that the nameplate wins
    UnitApproximate running currentUsually specified
    1.0 ton splitaround 5 to 7 A16 A C curve, double pole
    1.5 ton splitaround 7 to 10 A16 A C curve, double pole; 20 A where the unit’s rated current is higher
    2.0 ton splitaround 10 to 13 A20 A C curve, double pole

    Read the rated and maximum current from the unit’s nameplate or manual and use those, plus the cable size on the circuit. Tonnage is a cooling rating, not an electrical one, and two 1.5 ton units can differ.

    • Give the air conditioner a dedicated circuit. Sharing it with sockets means one appliance can trip the other, and it makes the rating harder to choose.
    • Use a double pole device on that circuit so the point can be isolated completely for service.
    • Check the cable. A 20 A MCB on a circuit wired for less is not a fix for tripping: it removes the protection the cable relies on.
    • If the unit trips the breaker only on start-up, that is a curve and coordination question. If it trips at random during running, treat it as a fault and have it looked at.

    MCB, RCBO, or both?

    An MCB handles overload and short circuit. It does not detect earth leakage, which is the fault that matters for shock protection. There are two normal ways to cover both.

    Two ways to build a domestic board
    ArrangementHow it behavesTrade-off
    RCCB at the board, MCBs on each circuitOne residual current device covers a group of circuits sitting behind itCheaper and compact, but an earth fault anywhere in the group takes out every circuit in it
    RCBO per circuitEach circuit has its own overcurrent and earth-leakage protection in one deviceCosts more and takes more board space, but a fault only disconnects the circuit that caused it

    Many boards use both: RCBOs on the circuits where nuisance disconnection is most disruptive, and an RCCB group for the rest.

    Our circuit-protection listing carries both. If you are deciding between the two, our RCCB guide covers what the residual current device is actually detecting and which sensitivity rating applies where.

    MCB ratings we carry

    Lauritz Knudsen Tripper series, C curve. Single, double, triple and four pole across the range.

    Current catalogue list prices per device. Send the full board schedule for a quotation against quantities.

    Where domestic boards usually go wrong

    1. Upsizing an MCB to stop nuisance tripping. The trip is information. Removing the protection does not remove the cause.
    2. Choosing the rating before the cable is decided. It is one decision, and doing it in the wrong order means the ceiling is set after the fact.
    3. Putting the air conditioner and the kitchen sockets on the same circuit, then wondering why the rating never feels right.
    4. Single pole devices on dedicated high-load appliance points, so the point cannot be isolated properly for service.
    5. Assuming an MCB provides shock protection. It does not, and an installation with no residual current device anywhere in it has a real gap.

    Common questions

    Which MCB is best for a home?
    There is no single answer, because a home needs several. Lighting circuits are usually 6 A, general socket circuits 10 to 16 A, and dedicated geyser and air-conditioner points 16 to 20 A on a double pole device, all C curve. Each rating has to fit the cable on that circuit, which is why the board schedule matters more than any general recommendation.
    Which MCB is required for a 1.5 ton AC?
    A 16 A or 20 A C curve MCB on a double pole device and a dedicated circuit covers most 1.5 ton split units, which draw roughly 7 to 10 A while running. Confirm against the rated and maximum current on the unit’s nameplate and against the cable size, because tonnage is a cooling rating and two 1.5 ton units are not necessarily the same electrical load.
    What happens if the MCB rating is too high?
    The cable loses its protection. A fault or overload that the cable cannot survive may not trip the device, so the cable heats up instead. This is the reason upsizing a breaker to stop nuisance tripping is the wrong response.
    Single pole or double pole for a geyser?
    Double pole is the usual specification for a dedicated geyser point. It disconnects live and neutral together, so the appliance is fully isolated for service rather than only having the live conductor broken.
    Do I need an RCCB as well as MCBs?
    An MCB cannot detect earth leakage, which is the fault involved in electric shock, so an installation with only MCBs has a genuine gap. The two normal arrangements are an RCCB covering a group of circuits, or an RCBO per circuit combining both functions. Which is right depends on the board and how disruptive a group disconnection would be.
    Why does my MCB trip only when the AC starts?
    That points at the starting surge rather than the running load, usually a curve or coordination question rather than a rating question. Have your electrician check the curve, the rating and the cable together. Fitting a larger device to make the symptom stop is the wrong fix.

    Price your distribution board

    Send the board schedule, or the list of circuits with their ratings and poles. We reply with current pricing on the MCBs, RCCBs and RCBOs we carry.

    Products covered in this guide

    Sources and further reading

    Specifications and catalogue list prices are those held against our catalogue records on the date shown above and can change. This guide covers product selection only; installation and testing must be carried out by a licensed electrician.

    New Delhi Electricals

    Your trusted partner for premium electrical solutions since 1998. Authorized retail partner for India's finest brands.

    Contact

    30 A Corner Market, Malviya Nagar
    New Delhi 110017
    9654102758

    Operating Hours

    Monday to Sunday

    10:00 AM to 7:30 PM

    Tuesday: half day, open till 4:00 PM

    Service Area

    Delhi NCR

    © 2026 New Delhi Electricals. All rights reserved.

    Authorised dealer · Malviya Nagar counter, serving Delhi NCR · Genuine branded products